Power systems, three-phase to machines

Power Systems carries 8–12 items, the largest area after Circuit Analysis and Mathematics, tied with Digital Systems. It starts where AC circuit power leaves off and adds three-phase connections, lines, transformers and rotating machines.

Updated Oct 29, 2026 · Not affiliated with NCEES.

What the area covers

Four subtopics in the July 2020 specification:

  • Power theory: power factor, single and three phase, voltage regulation.
  • Transmission and distribution: real and reactive losses, efficiency, voltage drop, delta and wye connections.
  • Transformers: single-phase and three-phase connections, reflected impedance.
  • Motors and generators: synchronous, induction and dc machines.

16 power systems problems

0 / 16 answered · 0 correct
Question 1 of 16 · Power Systems · 8–12 items

A 4-pole, three-phase induction motor runs at 1750 rpm on a 60 Hz supply. What is its slip?

Given
  • Rotor speed n = 1750 rpm
  • Frequency f = 60 Hz
  • Poles p = 4
FindSlip (%)

Solution

ns = 120f/p = 120 × 60/4 = 1800 rpm

s = (ns − n)/ns = (1800 − 1750)/1800 = 2.78 %

ns = 120f/p = 120 × 60/4 = 1800 rpm; s = (1800 − 1750)/1800 = 2.78 %.
This divides the slip speed by the rotor speed (50/1750); slip is referred to synchronous speed.
This uses ns = 3600 rpm, the synchronous speed of a 2-pole machine.
This is n/ns, the per-unit speed, which equals 1 − s.
Question 2 of 16 · Power Systems · 8–12 items

A transformer has 500 turns on the primary and 50 turns on the secondary. A 4 Ω load is connected to the secondary. What impedance is seen at the primary?

Given
  • Primary turns Np = 500
  • Secondary turns Ns = 50
  • Secondary load Zs = 4 Ω
FindImpedance referred to the primary (Ω)

Solution

Zp = (Np/Ns)2 · Zs

Zp = (500/50)2 × 4 Ω = 400 Ω

This squares the ratio upside down, (50/500)2 × 4; the high-turns side sees the larger impedance.
This uses the inverted ratio 50/500 without squaring it.
This scales by the turns ratio once; impedance scales with its square.
Zp = (Np/Ns)2 Zs = (500/50)2 × 4 = 100 × 4 = 400 Ω.
Question 3 of 16 · Power Systems · 8–12 items

The no-load voltage at the receiving end of a transmission line is 13.2 kV. Under full load, the voltage drops to 12.6 kV. What is the voltage regulation?

Given
  • No-load voltage Vnl = 13.2 kV
  • Full-load voltage Vfl = 12.6 kV
FindVoltage regulation (%)

Solution

VR = (Vnl − Vfl)/Vfl × 100 %

VR = (13.2 − 12.6)/12.6 × 100 % = 4.76 %

This divides by the no-load voltage; regulation is referred to the full-load voltage.
VR = (Vnl − Vfl)/Vfl = (13.2 − 12.6)/12.6 = 4.76 %.
This is Vfl/Vnl, a voltage ratio, not the regulation.
This is Vnl/Vfl; regulation subtracts 1 (100 %) from that ratio.
Question 4 of 16 · Power Systems · 8–12 items

A balanced three-phase delta-connected load draws 24 kW at 480 V line-to-line with a power factor of 0.8. What is the phase current in each delta branch?

Given
  • Real power P = 24 kW
  • Line-to-line voltage VLL = 480 V
  • Power factor pf = 0.8
FindPhase current in each delta branch (A)

Solution

Pph = 24 kW/3 = 8 kW, Vph = VLL = 480 V (delta)

Iph = Pph/(Vph · pf) = 8000/(480 × 0.8) = 20.8 A

This puts the whole 24 kW through one branch: 24,000/(480 × 0.8).
This is the line current, P/(√3VLLpf); in a delta each branch carries IL/√3.
Each branch takes 8 kW at 480 V: Iph = 8000/(480 × 0.8) = 20.8 A.
This divides the line current by 3; delta phase current is the line current divided by √3.
Question 5 of 16 · Power Systems · 8–12 items

A dc shunt motor with armature resistance 0.5 Ω draws 40 A from a 240 V supply. The field current is 2 A. What is the back EMF?

Given
  • Armature resistance Ra = 0.5 Ω
  • Line current I = 40 A
  • Supply voltage V = 240 V
  • Field current If = 2 A
FindBack EMF Eb (V)

Solution

Ia = IL − If = 40 − 2 = 38 A

Eb = V − IaRa = 240 − 38 × 0.5 = 221 V

Ia = 40 − 2 = 38 A; Eb = V − IaRa = 240 − 38 × 0.5 = 221 V.
This is the terminal voltage; the armature resistance drop always lowers the back EMF.
This uses the generator relation V + IaRa; in a motor the back EMF is below the terminal voltage.
This uses the generator relation with the full 40 A line current; a motor subtracts the armature drop, and 2 A of the 40 A feeds the field.
Question 6 of 16 · Power Systems · 8–12 items

A three-phase, 6-pole induction motor operates at 1164 rpm on a 60 Hz supply. What is the frequency of the rotor currents?

Given
  • Poles p = 6
  • Rotor speed n = 1164 rpm
  • Frequency f = 60 Hz
FindRotor current frequency fr (Hz)

Solution

ns = 120f/p = 1200 rpm, s = (1200 − 1164)/1200 = 0.03

fr = s · f = 0.03 × 60 Hz = 1.8 Hz

This is the stator supply frequency, which the rotor sees only at standstill.
This is (1 − s)f, the electrical equivalent of the rotor speed; rotor currents are at the slip frequency sf.
This is the rotor speed in revolutions per second (1164/60), not the frequency of the rotor currents.
ns = 120 × 60/6 = 1200 rpm; s = (1200 − 1164)/1200 = 0.03; fr = sf = 0.03 × 60 = 1.8 Hz.
Question 7 of 16 · Power Systems · 8–12 items

A balanced wye-connected three-phase generator has a phase voltage of 7.2 kV. If it delivers 15 MW at 0.85 power factor lagging, what is the line current?

Given
  • Phase voltage Vph = 7.2 kV
  • Real power P = 15 MW
  • Power factor pf = 0.85 lagging
FindLine current IL (A)

Solution

P = 3VphIph·pf, IL = Iph (wye)

IL = 15 × 106/(3 × 7200 × 0.85) = 817 A

This divides the correct current by √3 once more (817/√3 = 472 A), as if converting line to phase current in a delta.
This leaves out the 0.85 power factor: P/(3Vph).
I = P/(3Vph·pf) = 15 × 106/(3 × 7200 × 0.85) = 817 A; in a wye the line current equals the phase current.
This puts the phase voltage into the √3 formula, P/(√3Vphpf); √3 goes with the line-to-line voltage.
Question 8 of 16 · Power Systems · 8–12 items

A three-phase transformer bank consists of three single-phase transformers, each rated 7200:240 V. The primaries are connected in delta and the secondaries are connected in wye. What is the line-to-line voltage on the secondary side?

Given
  • Transformer rating = 7200:240 V each
  • Connection: delta primary, wye secondary
FindSecondary line-to-line voltage (V)

Solution

Vph,sec = 240 V (winding voltage)

VLL,sec = √3 × 240 V = 415.7 V

This adds three windings in series (3 × 240); a wye puts two phases between lines, displaced by 120°.
Each secondary winding gives 240 V phase-to-neutral; in wye, VLL = √3 × 240 = 415.7 V.
This is the voltage across one secondary winding, the phase voltage of the wye.
This divides by √3, the delta-to-wye direction applied backwards.
Question 9 of 16 · Power Systems · 8–12 items

Two 230 kV buses are joined by a lossless line with a series reactance of 120.0 Ω per phase, and both voltages are held at 230 kV line-to-line. What are the maximum three-phase real power the line can carry and the power at a 30° power angle?

Given
  • Bus voltages VS = VR = 230 kV line-to-line
  • Series reactance X = 120.0 Ω per phase (lossless)
  • Power angle δ = 30°
FindThree-phase Pmax and P at δ = 30° (MW)

Solution

P = (VSVR/X) sin δ (VLL values give the three-phase total)

Pmax = (230 kV)2/120 Ω = 441 MW, P30 = 441 × sin 30° = 220 MW

This multiplies VLL2/X by 3; the factor 3 belongs with the phase voltage, not the line voltage.
This uses the phase voltage 132.8 kV in V2/X without multiplying by 3; with line-to-line voltages the formula gives the three-phase total directly.
This uses cos 30° instead of sin 30°; real power follows sin δ.
Pmax = VSVR/X = (230 kV)2/120 Ω = 441 MW; P = Pmax sin δ = 441 × sin 30° = 220 MW.
Question 10 of 16 · Power Systems · 8–12 items

A three-phase transformer rated 5 MVA, 13.8 kV/480 V, has a 5.0 % impedance. Assuming an infinite source and a bolted three-phase fault at the 480 V terminals, what is the secondary short-circuit current?

Given
  • Rating S = 5 MVA
  • Voltage = 13.8 kV/480 V
  • Percent impedance Z = 5.0%
FindSecondary short-circuit current (kA)

Solution

Irated = S/(√3 · VLL) = 5 × 106 VA/(√3 × 480 V) = 6014 A

Isc = Irated/Zpu = 6014 A/0.05 = 120.3 kA

This multiplies the rated current by 0.05; a 5 % impedance divides it.
This uses the 13.8 kV primary rating, which gives the primary-side fault current.
This is the rated secondary current itself; the fault current is the rated current divided by the per-unit impedance.
Irated = 5 × 106/(√3 × 480) = 6014 A; Isc = Irated/Zpu = 6014/0.05 = 120.3 kA.
Question 11 of 16 · Power Systems · 8–12 items

A single-phase load draws 7.50 kW at 0.70 power factor lagging from a 240 V, 60 Hz supply. What capacitance connected in parallel raises the power factor to 0.95 lagging?

Given
  • Load real power P = 7.50 kW
  • Initial power factor pf1 = 0.70 lagging
  • Target power factor pf2 = 0.95 lagging
  • Supply voltage V = 240 V
  • Frequency f = 60 Hz
FindParallel capacitance C (µF)

Solution

QC = P(tan θ1 − tan θ2) = 7500 × (1.0202 − 0.3287) = 5186 var

C = QC/(ωV2) = 5186/(2π × 60 × 2402) = 238.8 µF

This sizes the capacitor from the drop in apparent power (kVA), not in reactive power.
QC = 7500(tan θ1 − tan θ2) = 5186 var; C = QC/(ωV2) = 5186/(377 × 2402) = 238.8 µF.
This cancels all of the original 7651 var, correcting to unity instead of 0.95.
This uses f = 60 Hz in place of ω = 377 rad/s in QC = ωCV2.
Question 12 of 16 · Power Systems · 8–12 items

A single-phase AC motor delivers 20 hp from a 240 V rms supply with 80 % efficiency and a lagging power factor of 0.85. Taking 1 hp = 745.7 W, what rms current does it draw?

Given
  • Output power Pout = 20 hp
  • Supply voltage V = 240 V rms
  • Efficiency η = 80%
  • Power factor pf = 0.85 lagging
  • Conversion 1 hp = 745.7 W
FindSupply current I (A)

Solution

Pin = Pout/η = (20 × 745.7 W)/0.80 = 18,643 W

I = Pin/(V · pf) = 18,643/(240 × 0.85) = 91.4 A

Pin = 20 × 745.7/0.80 = 18,643 W; I = Pin/(V·pf) = 18,643/(240 × 0.85) = 91.4 A.
This leaves out the power factor: I = Pin/V.
This uses the 14.9 kW output as the input power and ignores the 80 % efficiency.
This multiplies the output by the efficiency instead of dividing; the input power is larger than the output.
Question 13 of 16 · Power Systems · 8–12 items

An industrial facility is billed based on peak monthly kVA demand and total kWh consumption. The plant currently operates at a peak load of 500 kW with a power factor of 0.75. The facility manager proposes installing capacitor banks to improve the power factor to 0.95. Assuming the real power demand (kW) and hours of operation remain identical, which of the following describes the most likely impact on the utility bill?

Solution

S1 = 500/0.75 = 667 kVA → S2 = 500/0.95 = 526 kVA

kW × hours unchanged → kWh charge unchanged.

Real power stays at 500 kW; the demand charge falls because apparent power drops.
kWh depends on real power and hours, which stay the same; only the kVA-based charge falls.
This reverses the effect: the capacitors cut kVA, not kWh.
A 21 % cut in peak kVA is a significant change to a kVA-billed demand charge.
Peak kVA falls from 500/0.75 = 667 kVA to 500/0.95 = 526 kVA, while the kW and hours, and so the kWh, are unchanged.
Question 14 of 16 · Power Systems · 8–12 items

A single-phase transformer rated at 25 kVA has an efficiency of 96% at full load with unity power factor. What are the total losses at full load?

Given
  • Rating S = 25 kVA
  • Full-load efficiency η = 96 %
  • Power factor = 1.0
FindTotal full-load losses (kW)

Solution

Pout = S · pf = 25 kW, Pin = Pout/η = 26.04 kW

Ploss = Pin − Pout = 1.04 kW

This is the input power; the losses are the input minus the output.
This is 0.96 × 25, as if the rating were the input; it is an output, not a loss.
Pout = 25 kW at unity pf; Pin = 25/0.96 = 26.04 kW, so the losses are 26.04 − 25 = 1.04 kW.
This takes 4 % of the output; losses are 4 % of the input, which is larger than the output.
Question 15 of 16 · Power Systems · 8–12 items

A balanced three-phase motor on a 480 V line-to-line source draws 25 A line current at a power factor of 0.85. Its overall efficiency is 90 %, and it runs at 1750 rpm. What is the shaft output torque?

Given
  • Line voltage VLL = 480 V
  • Line current IL = 25 A
  • Power factor pf = 0.85
  • Efficiency η = 90 %
  • Speed N = 1750 rpm
FindOutput torque T (N·m)

Solution

Pout = η√3VLLIL·pf = 0.90 × √3 × 480 × 25 × 0.85 = 15.90 kW

ω = 2πN/60 = 2π × 1750/60 = 183.3 rad/s

T = Pout/ω = 15,900 W/183.3 rad/s = 86.8 N·m

This divides the output power by the speed in rpm; the torque formula needs ω in rad/s.
This leaves out the √3 in the three-phase input power.
Pin = √3 × 480 × 25 × 0.85 = 17.67 kW; Pout = 0.90 × 17.67 = 15.90 kW; ω = 1750 × 2π/60 = 183.3 rad/s; T = 15,900/183.3 = 86.8 N·m.
This uses the electrical input power and ignores the 90 % efficiency.
This divides by the efficiency instead of multiplying, so the output exceeds the input.
Question 16 of 16 · Power Systems · 8–12 items

A single-phase transformer has a turns ratio of 10:1 (primary to secondary). If the primary voltage is 2400 V, what is the secondary voltage under no-load conditions?

Given
  • Turns ratio = 10:1
  • Primary voltage Vp = 2400 V
FindSecondary voltage Vs (V)

Solution

Vs = Vp(Ns/Np) = 2400 V/10 = 240 V

This divides by 100, applying the 10:1 ratio twice.
Vs = Vp × Ns/Np = 2400/10 = 240 V.
This is the primary voltage; a 10:1 transformer steps it down.
This multiplies by the ratio, as if the transformer stepped up.

Answer every question to see your score

Three-phase in a few lines

For a balanced load, total power uses line quantities:

P = √3·VL·IL·cos θ S = √3·VL·IL

  • Wye: VL = √3·Vφ, IL = Iφ.
  • Delta: VL = Vφ, IL = √3·Iφ.

Balanced problems are easiest on a per-phase basis: convert to an equivalent wye, solve one phase, multiply power by three. Machines add a few more relations, starting with synchronous speed ns = 120f/p in rpm and slip s = (ns − n)/ns; the Handbook keeps them in the AC Machines section of its Electrical and Computer Engineering chapter (NCEES errata notice).

Common traps in power systems

  • Line or phase. The √3 sits on voltage in a wye and on current in a delta. Write down which quantity the stem gives before using it.
  • kW, kVAR, kVA. Real, reactive and apparent power form a right triangle; a power factor turns one into another. Transformer and generator ratings are in kVA.
  • Correction in kVAR first. A power-factor correction problem is solved as reactive power to cancel; capacitance comes after, from the voltage and frequency.
  • Poles, not pole pairs. In ns = 120f/p, p counts poles.
  • Which side of the transformer. An impedance moved across a transformer scales with the square of the turns ratio, and the direction matters.
  • Voltage regulation. It is measured against the full-load voltage: (VNL − VFL)/VFL.
  • Per-unit bases. Change the base before adding per-unit impedances from different nameplates.

Sources: Chapman, Electric Machinery Fundamentals; Glover, Overbye and Sarma, Power System Analysis and Design.

Other E&C areas

Power systems, quick answers

How many power questions are on the FE electrical exam?

8–12 of 110, roughly a tenth of a form.

Is the FE power section the same as the PE Power exam?

No. The FE covers fundamentals in about a tenth of one exam; the PE Electrical and Computer: Power exam is a separate licensing exam taken later.